InstallationSymmetra® MW800 kW400 VON OFFEMO

Pagina 2

4 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DConfigurationsThe UPS system can be configured in two ways. The Inverter Section can be pla

Pagina 3 - Contents

System Overview: ConfigurationsSymmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 5Configuration 2 (Inverter Section placed to the right)Width:

Pagina 4

6 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DExternal Bypass Static SwitchThe External Bypass Static Switch (External Bypass SSW) transf

Pagina 5

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 7Electrical InstallationElectrical Wiring PrincipleSee alsoSee separate guide on parallel op

Pagina 6

Electrical Installation: Electrical Wiring Principle8 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DExternal disconnection switchesInput/Ou

Pagina 7 - - SAVE THESE INSTRUCTIONS

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 9Top Cable EntryPreparing for top cable entry (Default)Cable entry in Top Cover of Input/Out

Pagina 8 - Installation safety

Electrical Installation: Top Cable Entry10 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DBattery cable connections (top cable entry)WARNING

Pagina 9 - System Overview

Electrical Installation: Top Cable EntrySymmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 11Feed the battery cables through the grommetsConn

Pagina 10 - Configurations

Electrical Installation: Top Cable Entry12 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DPE and AC cable connections (top cable entry)Feed

Pagina 11

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 13Bottom Cable EntryPreparing for bottom cable entryCable entry in bottom cover of Input/Out

Pagina 13 - Electrical Installation

Electrical Installation: Bottom Cable Entry14 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DPreparation for bottom cable entrya. Loosen bo

Pagina 14

Electrical Installation: Bottom Cable EntrySymmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 15Battery cable connection (bottom cable entry)WA

Pagina 15 - Top Cable Entry

Electrical Installation: Bottom Cable Entry16 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DConnect cables from battery system.Connect ca

Pagina 16

Electrical Installation: Bottom Cable EntrySymmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 17PE and AC cable connections (bottom cable entry

Pagina 17 - 44.45 mm

External Bypass Static Switch WiringWARNING!Before starting installation, check and test that all AC and DC power source breakers are in open position

Pagina 18 - Connect cables

Electrical Installation: External Bypass Static Switch WiringSymmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 19Top cable entryLoosen the 8

Pagina 19 - Bottom Cable Entry

Electrical Installation: External Bypass Static Switch Wiring20 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DBottom cable entryLoosen the

Pagina 20

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 21Communication cable overviewConnection plane0P0957X131X130ExternalEPOplaced onwallX133A21X

Pagina 21

22 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DRelay Board (Optional)Location of optional Relay Board123123123123123123NC 3123123

Pagina 22

Electrical Installation: Relay Board (Optional)Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 23Communication cables with optional Relay Bo

Pagina 23 - Battery 1

ContentsSymmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D iSafety ...1IMPOR

Pagina 24

Electrical Installation: Relay Board (Optional)24 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DRelay Board functionsThe Relay Board inform

Pagina 25 - Top cable entry

Electrical Installation: Relay Board (Optional)Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 25K11 Bypass operation • UPS is running in no

Pagina 27 - Communication cable overview

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 27SpecificationsLow-Impedance/High-Impedance EarthingThe Symmetra® MW is easily integrated i

Pagina 28 - Relay Board (Optional)

28 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DElectrical SpecificationsAC InputWARNING!Supply the UPS from a dedicated, 3 × 400/230 V, L

Pagina 29 - Shunt trip

Specifications: Electrical SpecificationsSymmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 29DC InputAC OutputAC Input External Bypass SSWThe

Pagina 30 - Relay Board functions

Specifications: Electrical Specifications30 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DNotes1. Nominal (Nom): Input current based on rat

Pagina 31

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 31Required Breaker Settings (400 V Systems)The Symmetra® MW is a fault-tolerant system capab

Pagina 32

Specifications: Required Breaker Settings (400 V Systems)32 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D22 kA is the maximum peak let-thr

Pagina 33 - Specifications

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 33Appendix System and Protective EarthingThe purpose of this appendix is to describe the sys

Pagina 34 - Electrical Specifications

ii Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DExternal Bypass Static Switch Wiring . . . . . . . . . . . . . . . . . . . . 18Top cable

Pagina 35 - Heat dissipation

34 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DTN SystemsCharacteristicsTN systems have one point connected directly to ground. All expos

Pagina 36 - Torque specifications

Appendix: TN SystemsSymmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 35Additional requirements for generating sets (IEC 60364-5-55 551.4.2)To

Pagina 37 - See also

Appendix: TN Systems36 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DThe characteristics of protective devices and the circuit impedances s

Pagina 38

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 37TT SystemsCharacteristicsTT systems have one point connected directly to ground and all ex

Pagina 39 - Appendix

Appendix: TT Systems38 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DWhen the protective device is an overcurrent protective device, it mus

Pagina 40 - TN Systems

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 39IT SystemsCharacteristicsIn IT systems the installation is insulated from earth or connect

Pagina 41 - Appendix: TN Systems

Appendix: IT Systems40 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DIn installations where the neutral is distributed, the following condi

Pagina 42

Residual Current SenseMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2Protective Earthing ConductorProtective

Pagina 43 - TT Systems

Residual Current SenseMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2Protective Earthing ConductorProtective

Pagina 44 - Appendix: TT Systems

Residual Current SenseMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2PEProtective Earthing Conducto rMain Pr

Pagina 45 - IT Systems

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D iiiIT Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pagina 46

Mains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2Main Protective Earthing TerminalExternal SSW-BypassSymmetra

Pagina 47

Residual Current SenseMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2PEProtective Earthing ConductorMain Pro

Pagina 48

Residual Current SenseMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2( Alternative to earth electrode )Earth

Pagina 50

02/2007990-1510D*990-1510D*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the fo

Pagina 52

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 1SafetyIMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONSThis guide contains important

Pagina 53

Safety: IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS2 Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510DInstallation safetyPress the

Pagina 54 - *990-1510D*

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D 3System OverviewUPS SectionsSerial numberThe serial number is stated on the type label behin